| DUCT TEMPERATURE TRANSMITTER(GDTO-420) |
|
|

|
|
"GDTO" Duct Temperature Transmitter is intended for Heating, Ventilating, and Air-handling units as follows ;
Supplying or Ventilating air sensing
Limit Sensor ( limiting lowest supplying air temperature )
Shift Sensor ( Revision of inside temperature complying with outside temperature )
Measuring Sensor ( Display sensing point or DDC auto control system ) |
 |
|
Supply Voltage
|
: 15 ~ 30V DC |
|
|
Output Signal
|
: 4 ~ 20mA
|
|
|
Sensing Range
|
: 0 ~ +70℃ , (-30 ~ +130℃) |
|
|
Accuracy
|
: ± 0.3°C |
|
Wiring
|
: 2 Wire
|
|
Sensing Time
|
: Approx. 30 sec. at 2m/ sec. Velocity
|
|
|
AMBIENT TEMPERATURE |
: -25 ~ +80 ℃ |
|
AMBIENT HUMIDITY |
: below 95%Rh |
|
Cable Fitting
|
: PF 1/2"
|
|
PROTECTION CLASS |
: IP 54 (EN60529)
|
|
Weight
|
: 0.19 Kg ( w/bracket ) |
|
| |
|

|
|
In case of controlling supplying air temperature : - In case of installing Fan at behind of the last Air control unit, install behind Fan - For other cases, install at least 1.5 meter distance behind from the last air control unit
In case of controlling Ventilating air temperature : - Install always at behind of Fan
| |
| DUCT TEMPERATURE TRANSMITTER(GDTO-105) |
|
|

|
|
"GDTO" Duct Temperature Transmitter is intended for Heating, Ventilating, and Air-handling units as follows ;
Supplying or Ventilating air sensing
Limit Sensor ( limiting lowest supplying air temperature )
Shift Sensor ( Revision of inside temperature complying with outside temperature )
Measuring Sensor ( Display sensing point or DDC auto control system ) |
 |
|
Supply Voltage
|
: 15 ~ 30V DC |
|
|
Output Signal
|
: Voltage 1 ~ 5 V DC |
|
|
Sensing Range
|
: 0 ~ +70℃ , (-30 ~ +130℃) |
|
|
Accuracy
|
: ± 0.3°C |
|
Wiring
|
: 2 Wire
|
|
Sensing Time
|
: Approx. 30 sec. at 2m/ sec. Velocity
|
|
|
AMBIENT TEMPERATURE |
: -25 ~ +80 ℃ |
|
AMBIENT HUMIDITY |
: below 95%Rh |
|
Cable Fitting
|
: PF 1/2"
|
|
PROTECTION CLASS |
: IP 54 (EN60529)
|
|
Weight
|
: 0.19 Kg ( w/bracket ) |
|
| |
|

|
|
In case of controlling supplying air temperature : - In case of installing Fan at behind of the last Air control unit, install behind Fan - For other cases, install at least 1.5 meter distance behind from the last air control unit
In case of controlling Ventilating air temperature : - Install always at behind of Fan
| |
|
| 查看评论 |
|
|
| 如果您用过本商品,或对本商品有所问题,欢迎发表自己的评论和问题。我们会及时对您提出的问题解答,对您的评论给予鼓励。谢谢对本站的支持。 |
|
|
|
1.根据您的需要产品,请选定型号;
2.与我司销售人员或技术人员确认您的产品的功能,参数.
3.根据产品名称,产品型号签订购销合同
4.汇款后将汇款底联和合同;收货人地址;开票信息;发货方式传真
直线传真:0760-88306579 分机传真:0760-88886370 88886371 88886372 88886373转807分机
上海办事处传真(FAX): 15382730581 |
| 售后服务热线:0760-0760-88886370 88886371 88886372 88886373-805 806 803分机 移动电话:15382730581 15377871867
公司直线传真:0760-88306579 公司分机传真:0760-88886370 88886371 88886372 88886373转807分机 联系电话(TEL): 15382730581 15377871867
邮政编码: 528400 公司邮箱:459382380@qq.com 客服QQ:459382380 和 568843411 |